Tell us what you want to power and for how long. We’ll estimate the nominal battery capacity to look for.

Your devices and backup time
Adjust usage, charge & losses

Using devices with different usage patterns? Add them separately in the planner.

From watts to watt-hours.

Required nominal Wh = average load in watts × hours ÷ (usable fraction × starting-charge fraction).

Average load = running watts × time-in-use fraction + station idle draw. Usage reduces average energy demand; it does not reduce the running-output rating a station needs.

A worked example.

A constant 100 W load plus 10 W of station idle draw for eight hours uses 880 Wh. At 80% usable capacity and full starting charge, the modeled nominal battery requirement is 880 ÷ 0.8 = 1,100 Wh.

At 50% starting charge, the same calculation needs 2,200 Wh of nominal capacity. A larger battery and a fuller battery are different ways to change available energy.

What this number leaves open.

A battery can have enough energy and still lack the output to start a motor. These quick tools do not know your devices’ startup demand. The transferred plan uses running watts as a placeholder for starting watts; replace it or add individual appliances before relying on a match.

Battery condition, temperature, inverter behavior and real appliance use can change runtime. No solar charging, extra batteries or replenishment is included. For a fridge or mixed appliance load, start with the fridge guide or the full planner.